The working paper The data heat island effect: quantifying the impact of AI data centers in a warming world (Marinoni and others, first posted March 21, 2026, revised April 21, 2026) used a reconstructed MODIS land surface temperature dataset from 2004 to 2024 and estimated that land surface temperature rises by about 2 °C on average after an SI data center starts operating, with effects up to about 10 km away.
- Home
- Heat Watch
- Method
Heat Watch · method
How the heat is read
Heat Watch uses one free NASA product, one rule and no estimate of its own. This page lists the product, the service, the units and the scale factor, how the site and its ring are chosen, how clouds are handled, how before and after are dated, and the limits. Data read November 17, 2026.
Method
Every step, dated
The same steps for every site. The server runs the same math on new summers.
- Product
- MOD11A2 version 6.1: MODIS/Terra Land Surface Temperature and Emissivity, 8-Day L3 Global 1 km SIN Grid. Each 8-day value is the average of the clear daily values in that window.
- Service
- The ORNL DAAC MODIS web service (TESViS, doi 10.3334/ORNLDAAC/1600), free and with no key: a 21 by 21 km box around each site, at most ten dates a request.
- Units
- Bands LST_Day_1km and LST_Night_1km, stored as integers. Kelvin is the value times 0.02. The fill value is 0 (no clear view that week) and valid values run from 7,500 to 65,535, as the service's own band list states. Shown in degrees Celsius (Kelvin minus 273.15).
- Times
- Terra passes at about 10:30 in the morning and 10:30 at night, local solar time, so day and night values are those moments, not the hottest or coldest hour.
- Summer
- The ten 8-day composites that start on day 161 to day 233 of each year, about June 9 to August 28, every year from 2012 to 2026. South of the equator these months are winter; the one such site says so.
- Site pixel
- The 1 km pixel whose center is nearest the site's coordinates on the Power Map.
- Ring
- Every pixel whose center is 5 to 10 km from the site's coordinates. Pixel centers are taken back from the sinusoidal grid (a sphere of 6,371,007.181 m) to latitude and longitude, and distances are great circle distances.
- Clouds
- A composite counts when the site pixel is clear and at least a quarter of the ring (and at least 10 pixels) is clear. A summer counts with three or more such composites; otherwise it shows as cloud.
- Gap
- The mean of site minus ring over the composites that count. The headline is the mean of the last three summers with a value.
- Before and after
- From the Power Map's dated timeline (Epoch AI): summers that ended before work began, against summers that began after the first building ran. Shown only with two or more summers on each side.
- Updates
- The server reads new summers from the same service as they come out, a few requests at a time, and keeps them for good: a finished summer never changes.
- Limits
- A 1 km pixel can mix a site with roads, fields or water. Land surface temperature is the skin of the ground, not the air. New roofs, paving and cleared land warm the ground on their own. Clouds leave gaps. A gap is a public signal, never proof that a site is running or how hard.
Context
The study, and the doubts
Heat Watch is not a copy of any study. This is what the 2026 study reported, and what its critics said.
Fortune reported on April 1, 2026 that the study had not been peer reviewed, and that some independent researchers note much of the heat may come from building on land that was once open ground and vegetation, not from the computers running inside.
Join the takeover
See every site
The ranked list of every SI data center by its summer heat gap.